产品描述
船用电缆短路载流量
1)下列短路电流适用于电缆正常工作时导体的最大额定温度为90℃的电缆.
The following short current ratings are for cables normally operating at a maximum conductor temperature of 90℃ .
2) 作为理论计算的基础,按照IEC60724规定,短路中导体的温升为250℃
As a basis of the calculation, the theoretical temperature that arises in the conductor during a short circuit is 250℃ in accordance with IEC 60724.
3) 乙丙橡胶绝缘在短路中所能承受的温度可高达250℃ .
EPR insulation are capable of withstanding of short term temperature up to 250℃ .
4) 短路时间为1秒时铜导体的短路电流值见下表;短路时间非1秒时,短路载流量通过下列公式计算: The short circuit current rating for copper conductors given in the table are values for 1 sec. and for other duration the current may be calculated by the following formular;
I
I = 1
It : 短路t秒时的电流 Short circuit current for t second (A)
I1 : 短路1秒时的电流 Short circuit current for 1 second (A)
t: 短路时间 Short circuit duration (second) 5) 假定的短路时间为0.2-5秒。 The duration of the short circuit based on these assumptions should be between 0.2 sec. and 5 sec.
导体截面积 Conductor area | 短路1秒时的电流 Short circuit current for 1sec. | 导体截面积 Conductor area | 短路1秒时的电流 Short circuit current for 1sec. |
mm2 | A | mm2 | A |
1 1.5 2.5 4 6 10 16 25 35 50 | 143 215 358 572 859 1431 2289 3577 5008 7154 | 70 95 120 150 185 240 300 | 10016 13593 17170 21463 26470 34340 42925 |